46 — electricalc
®
Pro
1. Set to 3-Phase:
(
)
3 PH
2. Enter Volts:

VOLT 230.
3. Enter HP:

IND* 50. HP
* If IND is not shown, press until IND is displayed in the upper left
area of the display.
4. Find Full-Load Current:
FLC 130. A
5. Find Dual Element Fuse size:
AMPS 227.5 dE
6. Display percent used:
%FLC 175. %
7. Find Single Element Fuse size:
(
SEFuse
)
AMPS 390. SE
8. Display percent used:
%FLC 300. %
9. Find Inverse Time Circuit Breaker size:
AMPS 325. b2
10. Display percent used:
%FLC 250. %
11. Find Instantaneous Trip Circuit Breaker size:

(InsTrip
)
AMPS 1,040. b1
12. Display percent used:
%FLC 800. %