6250 Servo Controller User Guide
1.
2.
3.
4.
5.
6.
7.
N
O
1234
DIP Switch
Factory Default Setting Shown
OFF OFF OFF Ø (default)
OFF OFF ON 1
OFF ON OFF 2
OFF ON ON 3
ON OFF OFF 4
ON OFF ON 5
ON ON OFF 6
ON ON ON 7
* Device address is checked upon power up or reset.
6250 PCA
NOTE: If Auto Baud is enabled, the 6250 performs its auto
baud routine every time it is powered up or reset. The 6250 is
capable of matching 1200, 2400, 4800, and 9600 baud. Once
the baud rate has been determined, the 6250 stores that baud
rate in non-volatile memory; therefore, Switch #4 should be set
to the OFF position after the baud rate has been determined.
Switch #3 Switch #2 Switch #1 Device Address
Change Switch #4 to the ON position.
Connect the terminal to the 6250's RS-232C serial port on
the AUX connector.
Power up the terminal.
Cycle power to the 6250 and immediately press the space
bar several times.
The 6250 should send a message to the terminal confirming
the baud rate (i.e., *9600). You should now be communicat-
ing to the 6250 via the terminal. If no baud rate messages is
received, verify steps 1 through 3 and repeat step 4.
Change Switch #4 to the OFF position.
Cycle power to the 6250. You should be communicating to
the 6250 via the terminal at the previously determined rate.
Following these steps to implement the Auto Baud feature:
Switch #4 ON = Auto Baud Enabled
Switch #4 OFF = Auto Baud Disabled (default)