Calculated Industries 6250 Guide de l'utilisateur Page 53

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 138
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 52
Basic 6250 Features
45
6250 Safety Features
To help ensure a safe operating environment, you should take advantage of the 6250's safety
features (see table). See Also refers you to the section in this user guide where you can find
more in-depth information about the feature (system connections and/or programming
instructions).
Feature Description See Also
Enable Input The enable input (ENBL), found on pin #14 on the AUX
connector, is provided as an emergency stop input to the
6250.
When you open the ENBL input, with respect to GND, the
analog output voltage between CMD+ and CMD- is clamped
to almost zero, and the shutdown outputs are activated on
both axes.
Clamping occurs independent of the
microprocessor and the DSP.
(The clamping circuit is also
connected to the watchdog timer; if the 6250's
microprocessor fails, the analog output voltage will be
clamped.)
Chapter 3:
System
Connections
Shutdown
Outputs
The 6250 uses the shutdown outputs to disable the drive if it
detects a problem. Two types of relay outputs are found on
both DRIVE connectors—SHTNC for drives that require a
closed contact to disable the drive, and SHTNO for drives
that require an open contact to disable the drive.
The shutdown relay outputs are essential for smooth power-
up and power-down of the system. The shutdown relay is
active (disabling the drive) when no power is applied to the
6250. When the 6250 is powered up, the shutdown relay
remains active until you issue the DRIVE11 command.
Chapter 3:
Motor Driver
Connections
Drive Fault
Inputs
The drive fault (DFT) inputs, found on pin #5 of both DRIVE
connectors, allows the drives to tell the 6250 if they
encounter a fault condition. When a drive fault occurs, the
6250 stops motion (at the rate set with the LHAD command)
and terminates program execution. No drive shutdown will
result unless it is initiated with an ERRORP error program.
Chapter 3:
Motor Driver
Connections
End-of-travel
Limit Inputs
End-of-travel limits prevent the load from crashing through
mechanical stops, an incident that can damage equipment
and injure personnel.
You can use hardware or software limits, as your application
requires. Hardware limits use the CW and CCW terminals on
the LIM1/2 connector. Software limits are set with the LSCCW
and LSCW commands.
Chapter 5:
End-of-Travel
Limits
User Fault
Input
Using the INFNCi-F command, you can assign any of the
programmable inputs the
user fault
function. You can then
wire the input to activate when an external event, considered
a
fault
by the user, occurs.
Chapter 5:
Input
Functions
Maximum
Allowable
Position Error
A
position error
(TPER) is defined as the difference between
the commanded position (TPC) and the actual position as
measured by the encoder (TPE). The maximum allowable
position error is set with the SMPER command. When the
maximum allowable position error is exceeded (usually due
to instability or loss of position feedback from the encoder),
the 6250 shuts down the drive and sets error status bit #12
(reported by the TER command).
If SMPER is set to zero (SMPERØ), the position error will not be
monitored.
Chapter 4:
Servo Tuning
Programmed Error-
Handling Responses
When any of the safety features listed above are exercised (e.g., ENBL input is opened, DFT input
is activated, etc.), the 6250 considers it an error condition. With the exception of the shutdown
output activation, you can enable the ERROR command to check for the error condition, and
when it occurs to branch to a preprogrammed response defined with the ERRORP command.
Refer to the Error Handling section in Chapter 7 for further information.
Vue de la page 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 137 138

Commentaires sur ces manuels

Pas de commentaire